How to Wire a Leviton Decora 3 Way Switch Correctly and Safely

Begin by identifying the common terminal on your device–it’s typically marked with a darker screw or labeled “COM” on the back. Attach the incoming power line (black or red) here first. Failure to connect this correctly will prevent the circuit from functioning. The remaining two screws are for travelers: these wires (often red and white, or both red) link the two controls in the setup. Use a multimeter to confirm which terminals are live at each position before proceeding.
Strip exactly 5/16 inch of insulation from each conductor to ensure solid contact without stray strands shorting adjacent terminals. Twist copper ends clockwise to match screw tightening direction, then loop them fully around the screw shaft. Finger-tighten first, then secure with a screwdriver until snug–over-torquing risks breaking the terminal plate. Check for loose strands escaping the wire nut connections upstream; even a single stray filament can cause intermittent operation or arcing.
Label both controls clearly: mark the top device as “Position A” and the bottom one as “Position B” on the wall plate. This prevents confusion during future maintenance. After restoring power, test each toggle position three times. Verify the load (light or outlet) responds instantly–delay or flickering indicates a loose traveler connection. If troubleshooting, disconnect power at the breaker, not just the toggle, to avoid accidental energization.
For models with integrated LEDs, ensure the neutral wire (white) is connected to the dedicated neutral terminal if present. Skipping this step will disable illumination while the rest of the circuit may still work. Ground wires (bare or green) must bond to the metal yoke or ground screw; never omit grounding, especially in damp locations. Use 14 AWG copper wire for 15-amp circuits or 12 AWG for 20-amp applications–mismatching gauge risks overheating.
In multi-gang boxes, separate travelers from adjacent circuits with wire nuts to avoid cross-talk. Keep conductors organized: run traveler wires along one side of the box, load wires along the other. If the circuit includes a dimmer, ensure compatibility with the fixture’s bulb type–LED replacements often require specific dimming curves to prevent buzzing or premature failure.
Installing a Dual-Control Circuit with Decora-Style Devices
Start by identifying the power source and load terminals on the first mechanism. The common terminal–typically marked darker or labeled “COM”–must connect to the incoming hot wire (black or red). Attach the traveler conductors (usually brass or lighter-colored screws) to the remaining terminals, ensuring they mirror the second device’s traveler connections.
Use this terminal configuration for both devices:
- Common (COM): Hot feed or load wire
- Traveler 1: Brass screw, often labeled L1 or A
- Traveler 2: Brass screw, often labeled L2 or B
- Ground: Green screw or bare copper wire
Shut off power at the circuit breaker before handling any conductors. Verify absence of voltage with a non-contact tester. Exposed ends should not exceed 1/4 inch to prevent accidental shorts. Secure all connections with wire nuts, twisting clockwise before capping.
For multi-gang installations, ensure travelers from both mechanisms share the same electrical box without crossing. Label each traveler pair with colored tape (e.g., red for L1, blue for L2) to avoid miswiring at the opposite end. Mistakes here create dead circuits or flickering loads.
Neutral conductors (white) typically bypass these devices unless integrating smart modules, which require a neutral path. If neutrals are present, splice them together in the box using a pigtail connection to maintain continuity. Never connect neutrals to traveler terminals.
Test the circuit after securing the devices into their jambs. Toggle both controllers; the load should activate regardless of position. If inconsistencies occur, recheck traveler routing–swapped wires cause one controller to work while the other fails. Ground wires must bond to metal boxes if present.
Calibration for dimming-capable models involves adjusting the slider or dial on both ends to sync brightness levels. Trial-and-error may be necessary to balance response times. Units with LED indicators should flash uniformly; irregular blinking signals miswired travelers.
Finalize by tucking conductors neatly into the box, avoiding pinched insulation. Install wall plates last to prevent dust accumulation in the mechanism. Reference the manufacturer’s color-coded diagram if labels wear off–travelers often use brass for L1/L2 and black for COM.
Identifying Conductors in a Dual-Control Circuit Setup

Begin by locating the common terminal–this conductor is typically darker (black or brass-colored) and often marked with a distinct label like “COM” or a similar abbreviation. In most three-terminal configurations, this is the only point that maintains continuous contact with the load or power source regardless of toggle position. Verify its role by testing voltage in both states: it should alternate between live and neutral when toggled.
Trace the traveler wires next–these are the paired conductors running between the two control points. They are usually of identical gauge and color (commonly red and black, sometimes with striped insulation) but may vary if the system was modified. Use a multimeter set to continuity mode to confirm their connectivity: each traveler should bridge the gap between the corresponding terminals on both devices when toggled correctly.
Distinguishing Travelers from Fixed Conductors
Examine the remaining terminals–these will either be brass or silver-toned screws, depending on the device model. The traveler pair will show no voltage differential when the circuit is toggled to the opposite position, while the common terminal retains partial tension. If one traveler exhibits intermittent voltage, it indicates cross-wiring; revisit connections to ensure proper isolation between the paired paths and the fixed conductor.
Label each identified conductor with masking tape or a marker to prevent confusion during reassembly. Note that in older installations, color coding may deviate–white insulation, for instance, might carry current instead of acting as a neutral return. Always prioritize functional testing over assumed color conventions, especially in pre-1980s builds where standards were less uniform.
When dealing with mixed-voltage systems (e.g., 120V and 240V sections in the same box), verify the common conductor’s role at both endpoints. Misidentifying this live path risks short-circuiting the system or creating a hazardous loop. For split-phase setups, the common wire should link directly to the breaker panel’s bus bar without interruption–any deviation requires an immediate review of junction points.
If the circuit includes an intermediary junction box, inspect all splice connections for corrosion or loose terminals. Oxidized contacts often mimic traveler behavior by introducing resistance, causing flickering or partial power loss. Clean terminals with a wire brush or replace damaged connectors to restore consistent conductivity across the entire dual-path network.
Final Validation Before Energizing
After securing all terminals, perform a final check using a non-contact voltage tester to confirm no stray currents remain exposed. Toggle the control points in sequence while observing the tester’s response–any unexpected activation signals a miswired segment. Only proceed once every conductor aligns with its designated function and the system behaves predictably across both positions.
Step-by-Step Guide to Connecting Dual-Location Light Controls

Verify the circuit breaker is off by testing the terminals with a non-contact voltage detector before handling any conductors. Identify the common terminal on each device–it’s typically marked with a darker screw or a distinct label–and the two traveler screws, which are brass-colored and positioned side by side. Connect the hot conductor from the power source to the common terminal of the first control; this ensures the circuit’s starting point is properly established. Secure the two traveler wires between the corresponding traveler terminals of both devices, maintaining consistent color coding (red to red, black to black) to prevent crossed connections.
Attach the neutral wire (if required) directly to the light fixture’s terminal block, bypassing both controls unless the setup includes a smart model requiring neutral for constant power. For standard mechanical setups, the load wire (returning to the fixture) connects to the common terminal of the second device. Use a torque screwdriver to tighten all terminal screws to 12-15 in-lbs, as specified in the manufacturer’s installation bulletin, to prevent overheating due to loose connections. Double-check each connection with a multimeter set to continuity mode to confirm proper contact before energizing the circuit.
| Wire Type | Terminal Type | Screw Color | Connection Sequence |
|---|---|---|---|
| Line (Hot) | Common (First Device) | Dark (Black or Copper) | Power Source → First Device |
| Traveler Pair | Traveler (Brass) | Brass | First Device → Second Device |
| Load | Common (Second Device) | Dark (Black or Copper) | Second Device → Fixture |
| Neutral | Fixture Terminal Block | White (or Gray) | Direct to Fixture (if needed) |
Trim excess conductor length to no more than 1/4 inch beyond the screw terminal to reduce stray wire exposure inside the electrical box. Fold wires neatly behind the device, ensuring they don’t interfere with mounting screws or adjacent terminals. Mount both units into their respective boxes using the provided screws, aligning the device flush with the wall plate. Restore power at the circuit breaker and test operation by toggling either device–both should independently turn the light on and off without flickering or delay.
If the setup includes dimming functionality, verify compatibility with the bulb type (LED, incandescent, halogen) and adjust the trim dial (located on the side of some models) to set minimum brightness levels, preventing flicker at low settings. For dual-voltage configurations (120V/277V), confirm the correct voltage rating is selected via the internal jumper before finalizing installation. Document the traveler wire colors and terminal assignments in a quick-reference sketch inside the service panel cover for future troubleshooting or upgrades.
After 24 hours of operation, inspect all connections for signs of overheating–discoloration, melting, or a burning odor indicate a loose terminal requiring immediate correction. Replace any damaged wire nuts or insulation stripped beyond 3/8 inch to maintain code compliance. If the circuit behaves erratically, disconnect power and systematically recheck each connection against the included schematic in the product’s instruction sheet, focusing on the common and traveler terminals first.